Water systems testing
Water supply systems inside buildings: hot and cold water systems. Testing of water quality and Legionella spp.
- Systems
- hot and cold water
- Testing
- Legionella spp.
- Frequency
- per buildingrisk assessment
When to test for Legionella?
Besides regular testing, we also recommend it in these situations.
Regulation NN 43/24 (in Croatian) (opens in a new tab)Every building
has its own testing plan
The frequency is set by the risk assessment.
- Positive or failed result
- Works or disinfection
- Start of season or downtime
- New building or new use
- Poor temperature or circulation
- Suspected legionellosis
What is tested
From the boiler room to the tap: we take the samples, the laboratory does the analysis.
We sample in the building
hot and cold water, points of use
We take it to the lab
NZZJZPGŽ
We send you the results
with an assessment of compliance with the regulations

Water systems · hot and cold waterLegionella and group A
Legionella spp.hot water
- Buildings with central hot water
- Hotels, campsites and similar
- Water temperature measured on site
Samplesafter flushing
- Cold water where it enters the building
- Hot water leaving the tank
- Hot water at the farthest point
- Hotels: two more from the end risers
Occupancy permittechnical inspection
- Group A and hydrocarbons (C10–C40)
- New builds and renovations
You get a test report for every sample
For each parameter, the report gives the test method, the maximum permitted value, the result and an assessment of compliance with the regulations.
| Parameter | Method | Limit |
|---|---|---|
| At the sampling point | ||
| Hot water temperature · farthest pointthermometer | thermometer | ≥ 50 °C |
| Laboratory | ||
| Legionella spp.Bacteria that multiply in hot water systems and can be passed on by breathing in aerosols. · cold water, inletHRN EN ISO 11731 | HRN EN ISO 11731 | < 100 cfu/L |
| Legionella spp.Bacteria that multiply in hot water systems and can be passed on by breathing in aerosols. · tank outletHRN EN ISO 11731 | HRN EN ISO 11731 | < 100 cfu/L |
| Legionella spp.Bacteria that multiply in hot water systems and can be passed on by breathing in aerosols. · farthest pointHRN EN ISO 11731 | HRN EN ISO 11731 | < 100 cfu/L |
| Legionella spp.Bacteria that multiply in hot water systems and can be passed on by breathing in aerosols. · end riser 1HRN EN ISO 11731 | HRN EN ISO 11731 | < 100 cfu/L |
| Legionella spp.Bacteria that multiply in hot water systems and can be passed on by breathing in aerosols. · end riser 2HRN EN ISO 11731 | HRN EN ISO 11731 | < 100 cfu/L |
Legionella spp.: limit of negligible contamination under the Croatian regulations (NN 43/24)
Contract partnerTeaching Institute of Public Healthof Primorje-Gorski Kotar County
Frequently asked questions
How often is Legionella tested?
There is no single frequency set for all buildings. For each one, it is set by its own risk assessment.
Is water quality tested too?
Yes. Along with Legionella, we test the water quality parameters (group A), as for drinking water.
Drinking water testingWhat is tested for an occupancy permit?
For new builds and renovations, at the technical inspection: group A and hydrocarbons (C10–C40).